< 1-channel isolated barrier
< 24 V DC supply (Power Rail)
< Logic input < Output 100 mA at 13 V DC
< Alternating outputs for the operation of solenoids with 2 coils
< High output power for IIB gas group
< Line fault transparency (LFT)
< Test pulse immunity
< Up to SIL 3 acc. to IEC/EN 61508
Pepperl Fuchs Solenoid Driver KFD2-SLD-Ex1.13100
Function
This isolated barrier is used for intrinsic safety applications.
The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area.
The device has 2 alternating outputs, in order to be able to operate a valve with 2 coils.
If both inputs are energized, then only output I is energized.
The device is immune to the test pulses of various control systems.
The line fault transparency function can display a line fault in the field by a change in impedance at the switching input of the solenoid driver.
A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.